ECPD with measuring/communication function RCD type F 30mA In: 16

Add to selection
General information
Ordercode YESSS
3132-1881
Product code
5TY13503MF16
EAN code
04047624417063
Product group
Earth leakage circuit breaker
Brand
Siemens AG
Type
ECPD COM 230VAC 75kA 1+N type F ...
ECPD with measuring/communication function RCD type F 30mA In: 16 ECPD with measuring/communication function RCD type F 30mA In: 16 A, 2
STOCK
IN STOCK
0 piece
Product description

ECPD with measurement and communication function RCD type F 30 mA In: 16 A, Un: 230 V AC, 75 kA 1+N in 2 MW Please consider wireless approval! list of countries: see certificates Electronic Circuit Protection Device SENTRON ECPD 5TY COM for combined protection against overload, short-circuit, and fault currents in only 2 MW. The multifunctional and communication-capable 5TY electronic circuit protection device offers many advantages in a single device. It is ultra-fast, up to 1000 times faster than comparable devices, pulse-proof, and selective for maximum protection. The ECPD can be individually configured by parameterization and is thus adapted to your application.Sustainability rethought: The combination of several functions on only 2 MW saves resources and costs (e.g. 80% less electronics, 90% less metal, 90% less plastic). In the surrounding application, you also benefit from lower energy demand, material savings (e.g. copper), and simplified wiring. The 5TY electronic circuit protection devices are available with various current ratings. Busbars, infeed terminals, and a locking device are available as accessories. SENTRON ECPD. All you need. And more.

Product specifications
Number of poles (total)
2
Rated voltage
230 V
Rated insulation voltage Ui
250 V
Rated impulse withstand voltage Uimp
4 kV
Rated current
16 A
Rated fault current
0.03 A
Leakage current type
F
Current limiting class
3
Rated short-circuit breaking capacity according to EN 61009
75 kA
Rated short-circuit breaking capacity Icn according to EN 61009-1
75 kA
Voltage type
AC
With interlocking device
Yes
Overvoltage category
3
Pollution degree
2
Width in number of modular spacings
2
Built-in depth
70 mm
Degree of protection (IP)
IP20