RCCB, 4-pole, type F, short-time delayed, In: 63 A, 300

Add to selection
General information
Ordercode YESSS
3071-2712
Product code
5SV36463
EAN code
04001869484518
Product group
Residual current circuit breaker (RCCB)
Brand
Siemens AG
Type
RCCB, short-time delayed
RCCB, 4-pole, type F, short-time delayed, In: 63 A, 300 RCCB, 4-pole, type F, short-time delayed, In: 63 A, 300 mA
STOCK
IN STOCK
0 piece
Product description

Residual current operated circuit breaker, 4-pole, type F, short-time delayed, In: 63 A, 300 mA, Un AC: 400 V Residual current operated circuit breaker SENTRON 5SV3 for comprehensive protection against electric shock for personnel and property. The RCCBs provide reliable safety in the installation due to the reach-around and touch protection that they contain as standard. Simply by operating a manual slide, you can remove the RCCB from the DIN rail or the busbar assembly without the use of a tool. Via the Data Matrix code on the device, you can gain fast access to all technical data in the Siemens Industry Online Support App. The SENTRON protective switching devices can be expanded by many additional functions with consistent accessories from the modular system. Optimized technology for your safety - only from Siemens.

Product specifications
Number of poles
4
Rated voltage
400 V
Rated current
63 A
Rated insulation voltage Ui
2000 V
Rated impulse withstand voltage Uimp
6 kV
Leakage current type
F
Selective protection
No
Short-time delayed tripping
Yes
Short-circuit breaking capacity (Icw)
10 kA
Surge current capacity
3 kA
Frequency
50 Hz
Additional equipment possible
Yes
With interlocking device
Yes
Width in number of modular spacings
4
Built-in depth
70 mm
Ambient temperature during operating
-25 - 45 °C
Pollution degree
2
Connectable conductor cross section multi-wired
0.75 - 35 mm²
Connectable conductor cross section solid-core
0.75 - 35 mm²
Rated fault current
0.3 A
Voltage type
AC
Explosion-proof
No
more specifications
^